| Test |
Procedure |
Results |
| Fire |
FM-4880 |
Passed: Class 1 Fire Rating of Insulated Wall or Wall and Roof / Ceiling Panels, Interior Finish Materials or Coatings, and Exterior Wall Systems |
| ASTM E84 |
Flame Spread: 25 or Less / Smoke Developed: 450 or Less |
| CAN/ULC-S101 |
Fire Endurance Tests: 10 min and 15 min stayed in place |
| CAN/ULC-S102 |
Flame Spread: 5, Smoke Developed: 135 for panel with facings |
| CAN/ULC-S127 |
Flame Spread: <500 for foam core |
| CAN/ULC S138 |
Passed: Fire growth of foamed plastic insulated building panels in a full scale room configuration |
| CAN/ULC-S134 |
Passed: Standard method of test for fire of exterior wall assemblies |
| NFPA 259 |
Tested for potential heat of building materials |
| NFPA 268 |
Passed: Standard test method for determining ignitability of exterior wall assemblies using a radiant heat energy source |
| NFPA 285 |
Passed: Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components |
| Structural |
FM-4881 |
Passed: Class +110/-154 Zone H Class +100/-140 Zone HM – LM |
| ASTM E72 |
Vacuum chamber tested. Panel load / span and deflection tables are available |
| Thermal Transmission |
ASTM C518 |
| Thermal Performance at 75° |
|
Thermal Performance at 35° |
| Thickness |
U-Factor |
R-Value |
Thickness |
U-Factor |
R-Value |
| 2 |
0.07 |
14.4 |
2 |
0.06 |
16 |
| 2.5 |
0.06 |
18.0 |
2.5 |
0.05 |
20 |
| 3 |
0.05 |
21.6 |
3 |
0.04 |
24 |
| 4 |
0.03 |
28.8 |
4 |
0.03 |
32 |
| 5 |
0.03 |
36.0 |
5 |
0.03 |
40 |
| 6 |
0.02 |
43.2 |
6 |
0.02 |
48 |
|
| Air Infiltration |
ASTM E283 |
0.003 CFM/ft² of Panel Area at 6.24 psf |
| Water |
ASTM E331 |
No uncontrolled water penetration at 20 psf differential pressure |
| AAMA 501.1 |
Dynamic water pressure testing – no sign of water leakage at 15 psf |
| Fatigue Tests |
Cyclic test to positive and negative wind loading to ± L/180 deflection |
The panels exceeded 2 million alternate cycles without failure or damage |
| Bond Strength |
ASTM D1623 |
Panels tested for tensile bond strength of metal to foam |
| Sample placed in an autoclave device and pressurized to 2 PSI at 212 °F for 2½ hrs |
| Skin Delamination |
|
No skin delamination with direct pull off pressure up to 1188 psf |